首页标题    产品中心    美标电缆    SER or SEU

SER or SEU

APPLICATIONS (suitable for use as follows :)

● Joysense Type SE, service entrance cable is used to convey power form the service 

drop to  the meter base and from the meter base to the distribution panelboard; 

however, it may be used in all applications where Type SE cable is permitted

● SE cable may be used in wet or dry locations at temperatures not to exceed 90℃

● Voltage rating is 600V

STANDARDS&FEFERENCES

Joysense Type SE cable meets or exceeds UL Standard 44 

for Type XHHW-2 conductors UL Standard 854, 

Federal Specification A-A 59544, and requirements of the NEC®.

CONSTRUCTION

Joysense Type SE cable is construted with sunlight resistant Type 

XHHW-2 conductors or Type THWN conductors. 

Aluminum conductors are AA-8000 series Aluminum Alloy, 

compact stranded. Joysense Type SE, Style R Cable assembly plus

 reinforcement tape are jacketed with gray sunlight resistant polyvinyl chloride (PVC).

Available as 2 conductor (2 insulated phase conductors, bare ground), 3conductor 

(2 insulated phase conductors, insulated neutral, bare equipment ground), or 4 conductor

 (3 insulated phase conducted, insulated neutral, bare equipement ground). 

Type SE, Style U Cable assembly plus an overall concentrically applied neutral and 

reinforcement tape are jacketed with gray sunlight resistant polyvinyl choloride (PVC).

SPECIFICATIONS

● SER Sample Specification: Cable shall be UL-listed Type SE, 

Style R, suitable for operation at 600V or less as specified in the NEC®. 

Conductors shall be Aluminum Alloy, weather resistant PVC jacketed, 

as manufactured by Joysense Company.

● SEU Sample Specification: Cable shall be UL-listed Type SE, 

Style U, suitable for operation at 600V or less as specified in the NEC®. 

Conductors shall be Aluminum Alloy, weather resistant PVC jacketed, 

as manufactured by Joysense Company.

 

 

WEIGHTS,MEASUREMENTS AND PACKAGING

CONDUCTOR SIZE/CONSTRUCTION

(AWG or kcmil)

NOMINAL

O.D.(mils)

ALLOWABLE AMPACITIES”

APPROXIMATE

 NET WEIGHT 

PER 1000ft(lbs)

60℃

75℃

90℃

DWELLING

SER ALUMINUM TOW CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “EZ-SE” )

6-6-6

650

40

50

60

-

150

4-4-4

745

55

65

75

-

203

4-4-6

745

55

65

75

-

203

2-2-2

864

75

90

100

100

290

2-2-4

864

75

90

100

100

290

2/0-2/0-1

1140

115

135

150

150

527

2/0-2/0-2/0

1140

115

135

150

150

527

4/0-4/0-2/0

1354

150

180

205

200

784

4/0-4/0-4/0

1354

150

180

205

200

784

SER THREE CONDUCTOR WITH BARE GROUND (GORMERLY REFERRED TO AS “FOUR CONDUCTOR” )

8-8-8-8

612

30

40

45

-

136

6-6-6-6

717

40

50

60

-

196

4-4-4-6

823

55

65

75

-

252

2-2-2-4

956

75

90

100

100

359

1-1-1-3

1079

85

100

115

110

449

1/0-1/0-1/0-2

1168

100

120

135

125

540

2/0-2/0-2/0-1

1264

115

135

150

150

653

3/0-3/0-3/0-1/0

1378

130

155

175

175

793

4/0-4/0-4/0-2/0

1503

150

180

205

200

968

250-250-250-3/0

1576

170

205

230

225

-

SER FOUR CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “FIVE CONDUCTOR” 452)

2-2-2-2-4

1059

75

90

100

100

452

2/0-2/0-2/0-2/0-1

1404

115

135

150

150

827

4/0-4/0-4/0-4/0-2/0

1672

150

180

205

200

1228

250-250-250-250-3/0

1847

170

205

230

225

-

SEU TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND 

(FORMERLY REFERRED TO AS “THREE CONDUCTOR” )

6-6-6

430×687

40

50

60

-

145

4-4-4

499×800

55

65

75

-

198

4-4-6

474×775

55

65

75

-

181

2-2-2

569×925

75

90

100

100

283

2-2-4

554×910

75

90

100

100

259

2/0-2/0-2/0

736×1221

115

135

150

150

514

2/0-2/0-1

720×1205

115

135

150

150

468

4/0-4/0-4/0

878×1462

150

180

205

200

765

4/0-4/0-2/0

835×1419

150

180

205

200

691

Allowable Ampacites:
Allowable ampacities shown are for general use as specified by the NEC® ,2008 Edition, section 310.15.

60℃-When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors.

75℃-When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.

Dweling –For units. Condutors shall be permitted at listed ampacitees as 120/240 volt, 3-wire, 

single-phase services and feeders.

All conductors are compact stranded construction comdlying with UL standard 44.