RHH or RHW or USE

APPLICATIONS (suitable for use as follows :)

● Joysense Type RHH or RHW-2 OR USE-2 conductors

 are used with conduit as specified in the NEC®1.

● May also be used as underground service entrance cable, 

for direct burial, at conductor temperatures not to exceed 90℃.

● When used as RHW-2 or USE-2 conductor temperatures 

shall not exceed 90℃ in wet or dry locations.

● Voltage rating for RHH or RHW-2 or USE-2 conductors is 600V.

STANDARDS&FEFERENCES

Joysense Type RHH or RHW-2 or USE-2 conductors meet or exceed 

UL Standard 44 (for RHH or RHW-2), UL Standard 854(for USE-2), 

Federal Specification A-A-59544, and requirements of the NEC®.

CONSTRUCTION

Joysense Type RHH or RHW-2 or USE-2 aluminum conductors are

AA-8000 seriesAluminum Alloy, compact stranded. 

Insulation is an abrasion, moisture, heat, 

and sunlight resistant black cross-linked polyethylene (XLP).

SPECIFICATIONS

Conductors shall be UL-listed Type RHH or RHW-2 or USE-2,

suitable for operation at 600 V or less in wet or dry locations,

including direct burial in the earth. Conductors shall be Aluminum Alloy, 

XLP insulated, as manufactured by Joysense Company.

 

 

WEIGHTS,MEASUREMENTS AND PACKAGING

CONDUCTOR 

SIZE

(AWG or kcmil)

INSULATION 

THICKNESS

(mils)

NOMINAL

O.D.(mils)

AMPACITIES*(AMPS)

APPROXIMATE 

NET WEIGHT 

PER 1000ft(lbs)

STANDARD 

PACKAGE

60℃

75℃

90℃

8

60

257

30

40

45

36

B

6

60

292

40

50

60

49

B

4

60

336

55

65

75

65

B

2

60

391

75

90

100

94

B

1

80

462

85

100

115

126

B

1/0

80

499

100

120

135

151

B

2/0

80

539

115

135

150

182

B

3/0

80

586

130

155

175

221

B

4/0

80

638

150

180

205

269

B

250

95

713

170

205

230

326

B

300

95

763

190

230

255

381

B

350

95

809

210

250

280

435

B

400

95

852

225

270

305

488

B

500

95

929

260

310

350

595

B

700

110

1100

310

375

420

829

C

750

110

1131

320

385

435

881

C

1000

110

1283

375

445

500

1145

C

Allowable Ampacites:
Allowable ampacities shown are for general use as specified by the NEC® ,2008 Edition, section 310.15.

60℃-When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors.

75℃-When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.

Dweling –For units. Condutors shall be permitted at listed ampacitees as 120/240 volt, 3-wire, single-phase services and feeders.

All conductors are compact stranded construction comdlying with UL standard 44.