RHH or RHW or USE
|
APPLICATIONS (suitable for use as follows :) |
● Joysense Type RHH or RHW-2 OR USE-2 conductors are used with conduit as specified in the NEC®1. ● May also be used as underground service entrance cable, for direct burial, at conductor temperatures not to exceed 90℃. ● When used as RHW-2 or USE-2 conductor temperatures shall not exceed 90℃ in wet or dry locations. ● Voltage rating for RHH or RHW-2 or USE-2 conductors is 600V. |
|
STANDARDS&FEFERENCES |
|
Joysense Type RHH or RHW-2 or USE-2 conductors meet or exceed UL Standard 44 (for RHH or RHW-2), UL Standard 854(for USE-2), Federal Specification A-A-59544, and requirements of the NEC®. |
|
CONSTRUCTION |
|
Joysense Type RHH or RHW-2 or USE-2 aluminum conductors are AA-8000 seriesAluminum Alloy, compact stranded. Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linked polyethylene (XLP). |
|
SPECIFICATIONS |
|
Conductors shall be UL-listed Type RHH or RHW-2 or USE-2, suitable for operation at 600 V or less in wet or dry locations, including direct burial in the earth. Conductors shall be Aluminum Alloy, XLP insulated, as manufactured by Joysense Company. |
WEIGHTS,MEASUREMENTS AND PACKAGING |
|||||||
CONDUCTOR SIZE (AWG or kcmil) |
INSULATION THICKNESS (mils) |
NOMINAL O.D.(mils) |
AMPACITIES*(AMPS) |
APPROXIMATE NET WEIGHT PER 1000ft(lbs) |
STANDARD PACKAGE |
||
60℃ |
75℃ |
90℃ |
|||||
8 |
60 |
257 |
30 |
40 |
45 |
36 |
B |
6 |
60 |
292 |
40 |
50 |
60 |
49 |
B |
4 |
60 |
336 |
55 |
65 |
75 |
65 |
B |
2 |
60 |
391 |
75 |
90 |
100 |
94 |
B |
1 |
80 |
462 |
85 |
100 |
115 |
126 |
B |
1/0 |
80 |
499 |
100 |
120 |
135 |
151 |
B |
2/0 |
80 |
539 |
115 |
135 |
150 |
182 |
B |
3/0 |
80 |
586 |
130 |
155 |
175 |
221 |
B |
4/0 |
80 |
638 |
150 |
180 |
205 |
269 |
B |
250 |
95 |
713 |
170 |
205 |
230 |
326 |
B |
300 |
95 |
763 |
190 |
230 |
255 |
381 |
B |
350 |
95 |
809 |
210 |
250 |
280 |
435 |
B |
400 |
95 |
852 |
225 |
270 |
305 |
488 |
B |
500 |
95 |
929 |
260 |
310 |
350 |
595 |
B |
700 |
110 |
1100 |
310 |
375 |
420 |
829 |
C |
750 |
110 |
1131 |
320 |
385 |
435 |
881 |
C |
1000 |
110 |
1283 |
375 |
445 |
500 |
1145 |
C |
Allowable Ampacites: 60℃-When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. 75℃-When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. Dweling –For units. Condutors shall be permitted at listed ampacitees as 120/240 volt, 3-wire, single-phase services and feeders. All conductors are compact stranded construction comdlying with UL standard 44. |